PUMP-TANK-A01 · WATER CONTROL

Dual-pump water supply controller PCBA

Published engineering candidate. Controller and cabinet integration, calibration and physical acceptance remain subject to validation. A duty/standby controller for pump manufacturers, water-treatment equipment and cabinet integrators. Pressure and tank-level inputs coordinate one running pump and one standby pump, automatic alternation, fault handling and operating records.

Dual-pump water supply controller PCBA
PCBA 3D rendering · isometric
24V
18–30V DC input
2 × 4–20mA
Pressure + level inputs
2 pumps
Duty / standby operation
200 × 150
mm · 4-layer PCB

Applications

Designed around indoor clean-water auxiliary supply and direct-on-line contactor control. Match the pump curve, source-water level, system pressure and independent cabinet protection to the installation.

Pump equipment OEM

Integrate pressure control, alternation, contactor feedback and local operating records into a packaged two-pump supply unit.

Tank-to-pressure-vessel supply

Coordinate source-tank level and delivery pressure. A low-level input inhibits pumping, while pressure hysteresis reduces unnecessary switching.

Water-treatment auxiliaries

Control clean-water feed and transfer auxiliaries. Independent level, pressure and motor-protection contacts remain in the cabinet.

Industrial washing & utility water

Provide local on/off pressure control for clean-water utility skids, with one pump operating and the other available for alternate duty.

Facility utility pump sets

Give maintenance teams local fault indications, accumulated runtime, starts and Modbus access to pump-set information.

Control-cabinet retrofit

Reuse suitable contactors, overload devices and hardwired interlocks, adapting the field wiring and parameter settings to the existing installation.

System architecture

24V powers the controller and low-voltage cabinet branches. Two 4–20mA channels acquire pressure and tank level; 24V digital inputs acquire permissions, feedback and overload contacts. Dry-contact outputs command external 24V DC contactor coils. Motor power remains in the cabinet.

Dual-pump supply architecture
Dual-pump supply architecture

Control functions

Alternation

Successful operating cycles alternate duty between pump 1 and pump 2; only one pump is commanded at a time.

Automatic fallback

Automatic operation can transfer to the available standby pump after a start failure or overload, respecting the full stop interval.

Pressure hysteresis

The baseline starts below 2bar and stops at 3bar. Settings are matched to the hydraulic system; this is on/off control.

Stop interval & feedback

The baseline stop interval is 30s, feedback confirmation 2s and pressure-rise observation 10s.

Fault interlocks

Low source level, overpressure, invalid or stale measurements, contactor feedback faults and storage faults inhibit operation.

Manual & reset behavior

Manual commands retain protections. Reset clears an eligible latched fault; a separate new enable command is required to run.

Automatic supply control sequence

  1. 01 · Permission

    Check independent protection, source water, sensors, contactor feedback and storage before accepting an automatic enable command.

  2. 02 · Pressure demand

    Start the available duty pump below the start-pressure threshold after the required stop interval.

  3. 03 · Start confirmation

    Check contactor feedback and pressure rise. Stop and mark the pump unavailable after a start failure or overload.

  4. 04 · Standby transfer

    In automatic mode, start an available standby pump after the full stop interval. The controller never commands both pumps together.

  5. 05 · Pressure reached

    Withdraw the pump command at the stop threshold; alternate duty after a successful supply cycle.

  6. 06 · Fault & reset

    Protections remain active. Clear an eligible latched fault after its cause is removed; issue a new enable command to resume.

Baseline control parameters

ParameterBaseline
Start / stop pressure2 / 3 bar
Minimum stop interval30 s
Contactor feedback confirmation2 s
Pressure-rise observation10 s
Simultaneous run commandsOne pump maximum
Reset & power-upDo not restore enable

Protection chain & fault handling

ConditionResponse
Low source / mechanical pressure / emergency stop / phaseIndependent cabinet contacts interrupt execution branches; the controller monitors permission.
Motor overload / start failureWithdraw the affected pump command; conditional standby transfer in automatic mode.
Invalid / stale analog measurementInhibit operation; read validity flags together with raw values.
Unexpected feedback / storage faultLatch outputs off; retain available fault information and apply fault-specific reset conditions.

Electrical design

The board uses STM32G071CBT6, a 24V input power stage, two protected current-loop inputs, isolated RS485, local buttons and nonvolatile storage. Download the fixed component selections and editable KiCad source.

228 electrical components · 59 MPNs · 189 SMT / 39 THT · 12 mating plugs

Functional areas & key components

Follow the signal path from field inputs through the controller to external contactor commands, with the motor power circuit located in the cabinet.

AreaComponents / interfacesPurpose
24V power & input protectionJ1 · F1 · Q1 · LM5164 · AP211218–30V input feeds 5V / 3.3V rails, with fuse, reverse-polarity and surge-protection components in the input branch.
Pressure & level acquisitionJ3/J4 · TPS26611 · TVS3301 · TLV9004Two protected, filtered and conditioned 4–20mA channels feed the MCU; calibrate zero and full scale separately.
Field digital inputsJ5/J6/J12/J13 · LTV-817-CRun permission, source level, pressure, overload, contactor feedback and cabinet-door commands.
Control & storageSTM32G071CBT6 · 24LC256 · J2Control state machine, persistent parameters and events; SWD firmware programming and debugging.
External commands & alarmG5Q-14 DC5 × 4 · J7/J8/J9/J10Relay contacts connect low-voltage control branches to external contactors and independent protection contacts.
Industrial communicationADM2795E · J11 · JP1Isolated RS485 for Modbus RTU; configure termination according to bus position.

Dimensions & mounting

The board is 200 × 150mm, 1.6mm thick, with four Ø3.2mm holes for M3 mounting. Hole-centre pitch is 192 × 142mm; each centre is 4mm from its adjacent edges. Reserve cabinet space for mating plugs, cable bends, component height and service access.

Dimensions & mounting

Interfaces & wiring

ConnectorPinsFunction
J1218–30V DC input
J253.3V-reference SWD
J3 / J43 eachPressure / level 4–20mA loops
J5 / J65 eachPermission, source, pressure, feedback, overload, remote inputs
J7 / J82 eachPump 1 / pump 2 dry contacts
J93Alarm changeover contact
J102Spare dry contact K4 COM / NO
JP12RS485 termination jumper
J113RS485 A / B / isolated reference
J126Cabinet control / STOP-health wiring
J132Independent first-phase-contact load branch

Use the pin-by-pin connector table and cabinet wiring guide. The PCB contacts switch 24V DC control coils; they do not switch the motor supply. Preserve the independent emergency-stop, phase, source-level, mechanical pressure and overload chain, plus contactor interlocking.

Complete connector pin schedule (45 rows)
ConnectorPinNet
J11VIN_RAW
J12GND
J21+3V3
J22SWDIO
J23SWCLK
J24NRST
J25GND
J31LOOP_PWR_P
J32AI_IN_P
J33GND
J41LOOP_PWR_L
J42AI_IN_L
J43GND
J51DI_PERMIT_FIELD
J52DI_SOURCE_FIELD
J53DI_PRESSURE_FIELD
J54DI_FB1_FIELD
J55GND
J61DI_FB2_FIELD
J62DI_OL1_FIELD
J63DI_OL2_FIELD
J64DI_REMOTE_FIELD
J65GND
J71K1_COM
J72K1_NO
J81K2_COM
J82K2_NO
J91K3_COM
J92K3_NO
J93K3_NC
J101K4_COM
J102K4_NO
JP11TERM_B
JP12RS485_B
J111RS485_A
J112RS485_B
J113ISO_GND
J121PANEL_AUTO
J122PANEL_STOP
J123PANEL_RESET
J124PANEL_MAN1
J125PANEL_MAN2
J126GND
J131PHASE_CHAIN_FIELD
J132GND

Firmware & records

Modbus RTU runs at 9600baud, 8E1, default slave 1. FC03 reads values, parameters and event data; FC06 queues control commands; FC16 writes complete parameter groups and the event selector. Unavailable pressure/level values are reported as null by the service client, with raw words and per-channel validity.

Nonvolatile records include configuration, pump starts, accumulated runtime, boot count and a 464-entry event ring. Event timing uses monotonic uptime plus boot count. Power-up does not restore an enable command.

Modbus addresses & commands

Addresses below are zero-based PDU addresses. Human register numbering is 40001 + PDU address; see the protocol download for byte order and complete fields.

FunctionPDU addressPurpose
FC030–31Status, measurements and operating statistics
FC03256–26813 configuration registers
FC062881 Auto / 2 Stop / 3 Reset / 4 Manual P1 / 5 Manual P2
FC16256–268Complete parameter-group write; requires stopped and disabled conditions
FC16512–513Set the 32-bit event selector
FC03528–547Read the selected event and found flag

Default 9600baud, 8E1, slave 1. A write echo confirms queuing; read state, enable and fault flags to confirm execution. Use RS485 on a tracked cabinet bus.

Integration

The reference system selects two Grundfos CM5-5 pumps, Schneider LC1D09BL 24V DC contactors, GV2L08 / LRD08 motor protection, RM17TG20 phase monitoring, WIKA A-10 pressure and LH-10 level transmitters, and a MEAN WELL HDR-100-24 control supply. The system BOM includes valves, tank, vessel, wiring and installation accessories.

Board outline: 200×150mm, four copper layers, 1.6mm high-Tg FR-4 and ENIG. SMT and THT coordinates are separated. The DFM files specify a 0.125mm stencil and six U1 filled, planarized, copper-capped thermal holes. Use the board drawings for mounting, polarity, pin 1 and conductor separation.

Manufacturing & assembly process

ItemSpecification
FR-4Tg ≥ 170°C · 4 layers · 1.6 ± 0.1mm
CopperOuter ≥ 35µm · inner nominal 35µm
ENIGNi 3–6µm · Au 0.05–0.10µm
Stencil0.125mm · laser cut / electropolished
U16 filled / planarized / copper-capped thermal holes
Assembly189 SMT / 39 THT · separate placement files

Analog calibration & commissioning

Electrical scaling is 0–10bar pressure and 0–100% level. Calibration coefficients reside in firmware Flash, separately from EEPROM operating parameters. Download the firmware package for full procedures and tools.

Acquire current samples

Keep pumping disabled. Apply 4 / 8 / 12 / 16 / 20mA to each channel and acquire at least 10 valid samples at distinct times per point.

Generate coefficients

Use calibrate_analog.py for a board-specific coefficient header and report. Fit 4 / 20mA; independently check 8 / 12 / 16mA.

Install & recheck

Rebuild the matching firmware with the coefficient header, program and read back, then use new samples to check engineering values and out-of-range responses.

System selections & integration

CategoryReference selectionIntegration point
Two pumpsGrundfos CM5-5 × 2Match the pump curve to required head, flow and hydraulic losses.
ContactorsSchneider LC1D09BL · 24V DCDry contacts command coils; retain hardwired pump interlocking.
Motor protectionGV2L08 / LRD08Set protection to the motor nameplate and coordination requirements.
Phase monitorRM17TG20Connect to the independent permission branch.
Pressure / levelWIKA A-10 / LH-10 · 4–20mASelect ranges for working pressure, tank height and wiring arrangement.
Control supplyMEAN WELL HDR-100-2424V DC with separate controller and execution-branch protection.

OEM development & deliverables

Board & interfaces

Adapt board dimensions, connector positions, sensor count and communication to the cabinet, with pin assignments and mating-plug selections.

Control & supervision

Define pressure and timing parameters, manual / automatic behavior, Modbus addressing, event display and equipment-specific fault responses.

Editable engineering files

KiCad schematic / PCB, component BOM, manufacturing and assembly files, firmware source / HEX / BIN, protocol, wiring, calibration and DFM documents.

Technical downloads

The published wiring and calibration instructions retain open bench, risk-review and response-testing items. Review these before build release. Download the complete technical archive or individual categories without registration. Files cover editable schematics and PCB, local libraries, component and system BOMs, Gerber/drill/placement data, firmware source and binaries, service tools, calibration, wiring and engineering records.

SHA-256 manifest ↓

New drawings & rendering downloads

Download the 3D images and mounting drawing separately. The existing complete engineering archive remains available.

Rendering SHA-256 manifest ↓

Discuss pump controller development

Send the water-supply arrangement, pump and contactor details, pressure/level ranges, cabinet interfaces, board dimensions and required quantities to define your OEM controller scope.

Discuss pump controller development ↗