PROCESS CONTROL · TANK-CTRL-A02

Heated-tank process control PCBA

Published engineering candidate. Prototype, system and EMC validation remain pending. Control temperature, liquid level, pressure and flow in one heated-water system. A 24 V board connects the field instruments, operator panel and external power cabinet, with detailed accessory selections and downloadable technical files.

Heated-tank process control board
100 L
70 L working fill
3 kW
230 V AC
20–85 °C
65 °C default
24 V DC
215 × 130 mm

Applications

Heated storage and mixing tanks

Use the 100 L atmospheric clean-water tank as the system example: 70 L working fill, 230 V / 3 kW heater, 65 °C default setpoint and a fixed-speed circulation pump. The process setting spans 20–85 °C.

Recirculating warm-water equipment

Temperature control combines two three-wire Pt100 probes with circulation flow proof. Continuous level measurement handles filling, while independent low/high level switches provide permissives and stop the inlet valve.

Equipment adaptations

Adapt the interfaces for other tank sizes, heat loads and pumping arrangements. Industrial furnaces need a separate high-temperature sensor front end, power-stage sizing and process protection design; this water-tank configuration uses Pt100 probes.

Board architecture

The 215 × 130 mm, four-layer board uses an STM32G474RET6 controller, two MAX31865 Pt100 interfaces, an ADS1115 analog front end and MCP4728-based analog outputs. TPS26600 input protection and TMUX7412F analog protection are included. Field I/O uses 24 V; mains power stays in the external cabinet.

Electrical interfaces

InterfaceQuantity / signalUse in the tank example
Power24 V DCJ1; external protected branch
Temperature2 × three-wire Pt100Main liquid temperature + independent process cross-check
Analog inputs4 × 4–20 mAAI1 pressure / AI2 level / AI3 flow; AI4 spare
Analog outputs2 × 0–10 VExpansion; unused for fixed-speed pump
Digital inputs8 × 24 V PNPLevel, flow, contactors, pressure, lid, E-stop, hardware permit
Digital outputs6 × low-sideSSR, contactor command, pump, fill valve, spare, alarm
Pulse inputs2 channelsExpansion
CommunicationIsolated RS485Modbus RTU operator panel

Control sequence

A start request moves through filling and circulation proof before heating. The PI loop defaults to Kp = 5 and Ki = 0.02, with a 2 s zero-cross SSR window. Tune the loop to the installed tank, mixing and thermal losses. Fault reset clears the fault latch; it does not start the heater.

  1. Stopped
  2. Fill to 70%
  3. Prove circulation
  4. Enable contactors
  5. Heat & hold
  6. Stop / latched fault

Process settings & permissives

Flow ≥3 L/min and a continuous 1 s flow-switch proof precede heating. Pressure ≥0.30 bar, software temperature ≥90 °C, lost permissives, stale sensor data, contactor feedback faults or a 30 min fill timeout stop the process. The independent STB trips at 95 °C and uses manual reset below 90 °C.

Accessory selection

The system selection contains 71 per-unit purchasing lines and 11 factory-tool lines. Models, quantities, installation constraints and manufacturer URLs are recorded for each item. The table below exposes every line; the workbook provides the full purchasing layout. Configured probes and custom metalwork use the listed ordering specifications and matching interface drawings.

Selection and installation notes are translated from the Chinese engineering source. Model codes, quantities and limits are unchanged; the original Chinese notes remain available in the Chinese page and purchasing workbook.

Field instruments & plumbing 16
ID / functionManufacturer / modelQuantitySpecification & installation
T1/T2
Main/cross-check liquid-temperature probes
ifm
TM4431 ↗
2 pcsPt100 Class A; G1/2; insertion 100mm; liquid temperature -40..150°C
3-wire connection: M12 1/2 on the same end, 3 on the other end, 4 insulated; position H300mm
T3/T4
Independent overtemperature probes
JUMO
902006/10-402-1003-1-9-100-104/000 ↗
2 pcs1×Pt100 3-wire; Ø9×100mm; G1/2 compression fitting; -40..400°C
Model recommended in the 701150 manual; confirm the current order code/probe combination with JUMO; install at H160mm near the heater
LT
Continuous level transmitter
ifm
PM1789 ↗
1 pc-5..100mbar; set 4–20mA to 0..100mbar; hot water 85°C
Flush-mounted at the bottom, H0; 16.30146mA≈800mm(ρ980); calibrate on the actual tank
PT
Circulation-loop pressure transmitter
ifm
PM1707 ↗
1 pc-50..1000mbar; set 4–20mA to 0..1bar
Branch downstream of the pump; AI1; measure the maximum normal pressure; alarm at 0.3bar
PS
Independent pressure-permissive switch
ifm
PI2799 ↗
1 pc-1..1bar; medium -25..125°C; PNP OUT1
Hnc; SP1=0.30bar, rP1=0.20bar; OUT1→KPH and DI5; do not use KP35
LSL/LSH
Low/high level switches
ifm
LMT100 ↗
2 pcsPNP; G1/2 sealing cone; clean-water medium up to 100°C
Low level H250: OUT1 wet=1; high level H680: OUT2 dry=1; hardware low-level permissive/fill stop
FT
Flow meter
ifm
SM6120 ↗
1 pcG1/2 DN15; 0.05..35L/min; EPDM; medium up to 90°C
OUT2=4–20mA/0..35; OUT1=Hno 3.0/2.5L/min; clean-water conductivity ≥20µS/cm
P1
Fixed-speed circulation pump
Grundfos
98485504 / COMFORT 15-14 B PM ↗
1 unit230V 50/60Hz; Rp1/2; port-to-port distance 80mm; apply the 2..95°C limit
Basic B model; do not use AUTOADAPT; short closed loop; verify 3..5L/min by measurement
YV1
Normally closed fill solenoid valve
Bürkert
20056292 / Type 6213 ↗
1 pcDN13 G1/2;EPDM;24VDC;0..10bar;-30..90°C
Install only on the cold-water supply; closes on power loss; upstream filtration and flow adjustment; confirm coil power for the final manufacturer order; valve current budget 0.75A
WYV1
Valve connector
Bürkert
314820 / Type 2518 ↗
1 pcDIN EN175301-803 Form A; 24VAC/DC; LED+varistor; 10A; IP65
Includes seal/screw; 24V; connect 1(+)/2(-)/PE; provide 0.75mm² field wiring
PA1
Aseptoflex weld-in adapter
ifm
E30122 ↗
3 pcsØ50mm Aseptoflex Vario; EPDM seal included
1 each for LT/PT/PS; follow the manufacturer's welding procedure and use the protective mandrel
PA2
Level-switch weld-in adapter
ifm
E43300 ↗
2 pcsG1/2 sealing-cone weld-in adapter
For LMT100 only; do not replace the sealing cone with a standard G1/2 sleeve
PA3
Flow-meter pipe adapters
ifm
E40199 ↗
1 pack2 pieces per pack; sensor G1/2 flat seal→pipe R1/2
Both ends of SM6120; check supplied flat seals/length; allow straight pipe 5D upstream and 2D downstream
V1..V4
Manual isolation/drain valves
Genebre
3028 04 ↗
4 pcsDN15 G1/2 standard bore Ø14; Kv15; brass/PTFE/NBR; 110°C
1 isolation valve each upstream/downstream of the pump, 1 fill isolation valve, 1 bottom drain valve; fit a locking catch to the drain handle
SF1
Fill-line Y-strainer
Genebre
2460 04 ↗
1 pcR/Rp1/2; 316/PTFE; PN40; removable, cleanable filter element
Install before the fill valve; keep out of the low-head circulation loop
LS6
Tank-lid position switch
Telemecanique Sensors
XCKM121 ↗
1 pcMetal roller limit switch; 1NC+1NO; Pg11; IP66
30° cam; closing the lid closes 13/14 NO→DI6; mount on a bracket at ≤60°C
Cabinet & protection 28
ID / functionManufacturer / modelQuantitySpecification & installation
Q0
Main isolator
Schneider Electric
A9S60232 ↗
1 pc2P 32A; DIN; lockable
Two-pole disconnection of 230V L/N; continuous PE
QF0
Main residual-current/overcurrent protection
Schneider Electric
A9DC3620 ↗
1 pc1P+N;C20;Type A;30mA;6kA
Dedicated 20A site circuit; L/N orientation per nameplate; do not route PE through the neutral terminal
QF1
Heater-branch circuit breaker
Schneider Electric
A9F84216 ↗
1 pc2P C16;Acti9 iC60H
3kW resistive load; 2.5mm²; test current at the 253V upper limit
QF2
Control-branch circuit breaker
Schneider Electric
A9F84204 ↗
1 pc2P C4;Acti9 iC60H
Power supply/pump/fan; measure HDR supply inrush and cold-start behavior
PSU
24V DIN power supply
Mean Well
HDR-100-24 ↗
1 unit24V 3.83A/92W;85..264VAC
Design peak budget ≤3.1A; inside cabinet ≤40°C; board eFuse cuts off OV30..36V
DC1..5
24V electronic branch protection
Phoenix Contact
2908262 / PTCB E1 24DC/1-8A NO ↗
5 pcs18..30VDC; set DC4 to 2A and the others to 1A; NO status contact
1 each for the PCB, HMI, sensors, safety chain, and combined valve/alarm branch; STB maximum 12W, do not set the safety chain to 1A; IN- powers the device itself only, load return goes to the 0V busbar
SSR1
AC heater SSR with heatsink
Omron
G3PE-225B DC12-24 ↗
1 pcZero-cross; single-phase 25A@40°C; 75..264VAC; built-in heatsink; DIN
Nominal 13.04A; control ≤7mA; B model; verify cabinet thermal test ≤40°C and check derating
K1/K2
Series heater contactors
Schneider Electric
LC1D25BD ↗
2 pcs24VDC coil; 3NO; AC1 40A≤60°C; auxiliary 1NO+1NC
Both L/N run in series through K1 and K2; built-in NC contacts for EDM, NO contacts in series→DI4
SR1
Emergency-stop/restart-monitoring relay
Schneider Electric
XPSUAF13AP ↗
1 pc24VAC/DC; dual NC inputs; monitored manual reset; 3NO safety outputs
A1 powered through STB+low-level+pressure permissives; 13/14→K1, 23/24→K2, 33/34→DI8
STB
Independent overtemperature limiter
JUMO
00564208 / 701150/8-01-0253-2001-25/005,058 ↗
1 unit2×Pt100 3-wire; AC/DC20..30V; STB O-function; includes approval configuration 058
Trips at 95°C/manual reset below 90°C; 14/16 closed when healthy; German by default, retain configuration records
KR1..9
Interface relays with bases
Phoenix Contact
2966171 / PLC-RSC-24DC/21 ↗
9 pcs24VDC input 9mA; 1CO; 6A; DIN
DO2, DO3, DO4, DO6: 1 each; 1 each for low-level, high-level, pressure and emergency-stop health; KR9 in parallel with DI8 ensures SR1 output ≥10mA
HMI
7-inch operator panel
Weintek
MT8072iP V2 ↗
1 unit800×480; 24V350mA; COM2 RS485; cutout 192×138mm
19200/8E1; station 1; connected to PCB; Windows EBPro 6.10.02.421
S0
Dual-NC emergency-stop button
Schneider Electric
XB5AS8444 ↗
1 setØ22/40mm; twist release; 2NC
2NC to the two SR1 channels; fit a yellow emergency-stop legend plate
S0A
Additional NC contact for emergency-stop monitoring
Schneider Electric
ZBE102 ↗
1 pc1NC screw-terminal contact block; XB5 compatible
DC5 third contact→P_ES health; DI7/KR8/valve supply; check mechanical synchronization after assembly
S1/S2
Hardware reset buttons
Schneider Electric
XB5AA61 ↗
2 pcsBlue momentary; 1NO; Ø22
1 resets SR1 (through EDM), 1 provides external STB reset; do not reuse as software start
HLA
Red fault indicator
Schneider Electric
XB5AVB4 ↗
1 pc24VAC/DC LED;Ø22
Powered by the KR4 DO6 alarm contact; label as fault
HA
Fault buzzer
Schneider Electric
XB5KSB ↗
1 pc24VAC/DC; ≤28mA; Ø22; continuous/intermittent
Powered by KR4 alarm contact; continuous warning; DO6 does not provide a mute command
ENC
Steel control enclosure with mounting plate
Schneider Electric
NSYS3D8630P ↗
1 set800×600×300mm; original enclosure IP66; mounting plate included
Complete-cabinet target IP54 after HMI/fan installation; keep away from the tank steam outlet
FAN
Filter fan and outlet grille
Schneider Electric
NSYCVF85M230PF ↗
1 set230VAC; 85m³/h; G2 filter; IP54; outlet grille included
Lower intake/upper exhaust; cutout per delivered drawing; test temperature rise with a clogged filter/stopped fan
TH
Fan thermostat
Schneider Electric
NSYCCOTHO ↗
1 pc0..60°C; NO contact; DIN
Set fan start to 35°C; not for process-temperature protection
XTG
Gray DIN terminals
Phoenix Contact
3209510 / PT 2.5 ↗
56 pcs2.5mm² Push-in; 24A; 800V; width 5.2mm
Group per system wiring list; keep mains and 24V groups separate
XTB
Blue DIN terminals
Phoenix Contact
3209523 / PT 2.5 BU ↗
24 pcs2.5mm² Push-in;24A
Separate N and 0V zones; do not bridge the terminals
XTPE
PE DIN terminals
Phoenix Contact
3209536 / PT 2.5-PE ↗
12 pcs2.5mm²; yellow/green; rail grounding
Cabinet/door/tank/heater/pump/lid switch/probe head/sensor housing etc. per grounding schedule
XTEND
Terminal end plates
Phoenix Contact
3030417 / D-ST 2.5 ↗
12 pcsGray; matched to PT2.5
Fit at every exposed group end; do not omit
XTCLIP
DIN end stops
Phoenix Contact
3022276 / CLIPFIX 35-5 ↗
16 pcsNS35 end stop
8 rail sections, 2 per section
XTBUS
Terminal jumpers
Phoenix Contact
3030213 / FBS 10-5 ↗
4 pcs10 positions, 5.2mm; matched to PT2.5
Bridge equal potentials only; follow manufacturer derating after removing pins
RAIL
35mm perforated DIN rail
Phoenix Contact
0801733 / NS35/7.5 PERF 2000MM ↗
2 lengths2m×35×7.5mm; galvanized steel
Total cut length ≤3m; see layout for 8 section lengths; deburr cut ends
DB9
Panel-side RS485 connector
Phoenix Contact
2761499 / SUBCON9/F-SH ↗
1 pcDB9 female; individual screw terminals for all pins; shielded housing
pin2=D+, pin1=D-, pin5=GND; connect shell to shield, not to 24V
Cables, harnesses & assembly 21
ID / functionManufacturer / modelQuantitySpecification & installation
WC1
M12 sensor cables
ifm
EVT001 ↗
8 cablesA-coded 4-pin straight female; 5m; no LED; PVC; -25..100°C
T1/T2/LT/PT/PS/LSL/LSH/FT; each cable ≤5m after cutting; mark wire ends
WC2
High-temperature cable for independent probes
LAPP
00460033 / ÖLFLEX HEAT 180 SiHF 4G0.75 ↗
10m4G0.75mm² silicone; 180°C
T3/T4: 5m each; brown/blue/black for 3-wire RTD, PE to metal head only; equal lengths and cross-sections
RS485
RS485 cable
Belden
3106A.00152 ↗
2m120Ω; 22AWG twisted pair+reference+shield; maximum 60°C
Supplied as a 152m reel or a 2m cut from an authorized channel; keep away from heater wiring; single-point shell PE
ACIN
Main power lead
LAPP
1119403 / ÖLFLEX CLASSIC 110 3G2.5 ↗
3m3G2.5mm²;300/500V
Dedicated fixed 20A site circuit; no standard 10A/16A plug; nominal outside diameter 8.0mm
HEATWIRE
Heater lead
LAPP
0046020 / ÖLFLEX HEAT180 SiHF 3G2.5 ↗
3m3G2.5mm²; silicone 180°C; 300/500V
Junction box ≤100°C; protective earth on metal housing; do not suspend the load by the cable
PUMPWIRE
Pump/valve/lid-switch leads
LAPP
0046002 / ÖLFLEX HEAT180 SiHF 3G0.75 ↗
9m3G0.75mm²;180°C
3m each; lid switch needs only 2 cores+PE; do not use PE as a signal conductor
GLAND16
M16 cable glands
LAPP
53111010 / SKINTOP ST-M16×1.5 ↗
13 pcsClamping Ø4..10mm; gray; PA
8 M12 cables+2 independent RTDs+pump+valve+lid switch, total 13; separate Pg11 gland at the lid-switch end
GLAND20
M20 cable glands
LAPP
53111020 / SKINTOP ST-M20×1.5 ↗
2 pcsClamping Ø6..13mm
1 each for main power/heater; matching locknuts/seals
FERRULE075
0.75mm² ferrules
Phoenix Contact
3200519 / AI0.75-8 GY ↗
180 pcsTube length 8mm; strip wire to the terminal's specified length
For 0.34mm² sensor wires, do not force-fit 0.75 ferrules; select separate 0.34 ferrules
FERRULE25
2.5mm² ferrules
Phoenix Contact
3200522 / AI2.5-8 BU ↗
36 pcsTube length 8mm
Heater/main-power/grounding schedule; verify crimp pull strength
INTERNALWIRE
Internal cabinet wiring kit
Purchase to this project's drawings/specifications
TANK-WCAB-A02
1 packH07V-K 2.5 brown 5m/blue 5m/yellow-green 5m; 0.75 brown 10m/blue 15m/black 15m; 0.34 shielded signal extension ≤2m
Specify IEC60228 Class5; inside cabinet ≤60°C; mains and low-voltage signals in separate ducts
DUCT
Covered wiring duct
Purchase to this project's drawings/specifications
TANK-DUCT-A02
1 packFlame-retardant PVC V0; 40×60×2000mm, 2 lengths; slot pitch 8mm; covers included
Cut per cabinet drawing; separate AC/DC ducts; 20% spare capacity
GLANDKIT
Gland locknuts/plugs
Purchase to this project's drawings/specifications
TANK-GLANDKIT-A02 ↗
1 packM16 locknuts 13/M20 locknuts 2/EPDM panel seals 15; lid-switch Pg11 gland LAPP 53015020(Ø4..10)1 and EPDM face seal 1; M16 waterproof blanking plugs 2
Match LAPP gland thread type; Pg11 gland only for the XCKM121 field port; verify IP54 after cabinet cutouts; do not pass multiple cables through a standard single-hole gland
TINYFERRULE
Fine-wire sensor ferrules
Purchase to this project's drawings/specifications
TANK-AI0.34-8-A02
64 pcsTin-plated copper; 0.34mm²/8mm; insulated collar; DIN46228-4
For EVT001 0.34mm² wires only; terminal/wire pull-out test
PEKIT
Protective-earthing hardware
Purchase to this project's drawings/specifications
TANK-PEKIT-A02
1 packA2 M6×16 bolts 12/toothed washers 24/M6 nuts 12/tin-plated copper 2.5mm²-M6 ring terminals 24/yellow-green flexible door bonding strap 2.5mm²×300mm
Remove paint at dedicated PE studs, use double toothed washers; secure against loosening; connection target ≤0.1Ω per test plan
PCBMOUNT
PCB supports and touch-protection cover
Purchase to this project's drawings/specifications
TANK-PCBMOUNT-A02
1 setM3 male/female brass standoffs 12mm×4; M3×8 A2 screws 8/insulating shoulder washers 4; clear PC V0 cover 225×140×35mm
PCB mounting-hole pattern: 206×121mm; installed inside the complete cabinet; do not bond 24V copper to PE; ventilated and protected against dropped screws
SEALKIT
Pipe/flange sealing and fastener kit
Purchase to this project's drawings/specifications
TANK-SEALKIT-A02
1 packDN65 PN16 EPDM full-face gasket 1+spare 1/316 M16×60 bolts 4+nuts 4+washers 8; G1/2 FKM flat seals 4; PTFE tape 12mm×0.1mm×10m, one roll
Confirm flange GB/T9124.1 dimensions in agreed drawings; no PTFE tape on ifm sealing cones; check manufacturer-supplied seals separately at receiving
LABEL
Labeling and fastening consumables kit
Purchase to this project's drawings/specifications
TANK-LABEL-A02
1 packWire markers 200/device labels 80/yellow emergency-stop plate 1/hot-surface labels 4/equipment nameplate 1/316 pipe clamps DN15×8/cable ties 100/tie mounts 20/DIN mounting M4 sets 32
Serial number/3kW230V/atmospheric pressure/process ≤85°C; water- and heat-resistant labels; keep ties away from hot pipes
WT3T4
Independent RTD harness assembly
Purchase to this project's drawings/specifications
TANK-WT3T4-A02
2 cables4G0.75 silicone stock 00460033, 5m each; RTD 3-core terminals, PE to connector shell
T3→STB1/2/3, T4→6/7/8; same-end wire pairs to 2/3 and 7/8
HARNESS
Cabinet harness assembly/terminal labeling
Purchase to this project's drawings/specifications
TANK-WIRESET-A02
1 setBuild line by line from the system-wiring CSV; low-voltage signals 0.75/sensors 0.34; mains 2.5; match all terminals and wire numbers
Raw materials counted separately; do not count materials again in labor items; 100% continuity/miswiring/PE inspection
JUMPER
Termination jumper and HMI resistor
Purchase to this project's drawings/specifications
TANK-TERM-A02
1 pack2.54mm shorting cap 1; 120Ω1%0.25W axial resistor 1; insulating heat-shrink sleeves 2
Close PCB JP1; at the HMI DB9 1/2, add 120Ω; terminate at the two bus ends only
Custom tank / heater / piping 6
ID / functionManufacturer / modelQuantitySpecification & installation
TANK
Atmospheric tank assembly
Purchase to this project's drawings/specifications
TANK-V100-A02
1 set316L; inner Ø400×effective straight height 800; shell 2mm/bottom 3mm; volume 100.53L; insulation 25mm; legs 250mm
Working volume 70L; overflow H720; open DN25 vent without a valve; matching port schedule/dimensional drawing
H1
Immersion heater
Purchase to this project's drawings/specifications
TANK-H1-230-3000-A02
1 set230V/3kW±3%; 316L Ø14; 3U; cold section 35/straight sections 310, 285, 260/U-bend R20; insertion from outer end 372; bundle diameter ≤56; DN65PN16 flange
H100; total effective length ≥1.898m; parallel power sections 1080/1000/920W; nominal surface load ≤3.6W/cm²; PE stud; IP65 junction box; verify sample fit
PIPE
DN15 circulation/fill/drain pipe kit
Purchase to this project's drawings/specifications
TANK-PIPE-DN15-A02
1 set316L pipe Ø21.3×2; circulation total length ≤2m/≤4 bends; ISO7-1 R/Rp1/2; 4 detachable union sets
No filter/check valve in the circulation loop; separate flow adjustment+check valve on the cold-water fill side; pipe section dimensions per P&ID
LIMIT
Fill-flow restriction-orifice assembly
Purchase to this project's drawings/specifications
TANK-ORIFICE-2P6MM-A02
1 pc316L orifice plate; bore Ø2.6±0.05; DN15; removable
Cold-water inlet 1..3bar, expected 2.8..4.8L/min; measured flow ≤5L/min; 30min fill timeout; 70L in about 25min
CHECK
Cold-water fill check-valve assembly
Purchase to this project's drawings/specifications
TANK-NRV-DN15-A02
1 pcDN15 R/Rp1/2; 316L/EPDM; PN10; cracking pressure ≤0.05bar; medium 120°C
Supplier to quote this complete specification and provide certificates; keep out of the circulation loop
INVENT
Vent/overflow scald-protection drain kit
Purchase to this project's drawings/specifications
TANK-VENT-OVERFLOW-A02
1 setDN25 open gooseneck vent with removable coarse mesh; DN25 overflow to a safe tundish; total length of each ≤1m
Two independent outlets without valves or fine filters; scald guard at discharge; do not seal the lid
Factory tools 11
ID / functionManufacturer / modelQuantitySpecification & installation
WELD
Aseptoflex welding mandrel
ifm
E30452 ↗
1 pcG1 Aseptoflex Vario; matched to E30122
Unscrew after factory welding, clean and inspect sealing surfaces; not supplied with the product
DBG
Programming/debug probe
ST
STLINK-V3MINIE ↗
1 setSTDC14 cable included; adapt to the board J2 five-pin connector
J2=3V3 reference/SWDIO/SWCLK/GND/NRST; power the board from 24V; do not power it from the debug probe
IOSET
Sensor configuration kit
ifm
ZZ1060 ↗
1 setAL1060+E12689+EVC012;USB IO-Link
One-time factory equipment; moneo configure free; add E80121 if the available power is insufficient
CAL1
Current/voltage calibrator
Fluke
715 ↗
1 unit4/12/20mA and 0/5/10V tests
Valid traceable calibration certificate required; for AI/AO
CAL2
Pt100 simulator/calibrator
Fluke
724 ↗
1 unitPt100 3-wire simulation; 20/65/85°C
Test MAX31865 inputs and both STB channels
REF
Actual-tank reference thermometer
Fluke
1551A-12 ↗
1 pc-50..160°C; 12-inch probe; calibration certificate included
Compare in a stirred water bath; probe immersion depth per manufacturer requirements
DMM
Digital multimeter
Fluke
87V ↗
1 unitValid calibration; DC voltage/resistance
Measure 24/12/5/3.3V and AO; use safety test leads
USB485
Isolated USB-RS485 adapter
Waveshare
USB TO RS485 (B) ↗
1 pcIsolated type; 19200/8E1
Use at a different time from the HMI; connect D+/D-/GND; do not connect VCC
IOPS
External IO-Link power supply
ifm
E80121 ↗
1 pc24VDC M12 A-coded power supply
Required when ZZ1060 power is insufficient; not supplied with the product
TESTFIX
Functional test fixture
Project-specific custom item
TANK-FCT-A02
1 setSWD adapter/J1..J15 connections/LED load 9mA/DI24V switches/5m high-temperature sensor cables
See factory-test procedure; do not connect the actual heater; test matrix wiring before applying power
WIN
Configuration workstation
Existing factory equipment or locally provided
Windows11 x64 / EBPro6.10.02.421 ↗
1 unitUSB/Ethernet; 8GB RAM; offline software
EBPro/JUMO/moneo configuration; USB and Ethernet interfaces

Installation & wiring

Supply the board at J1 with 24 V DC and 0 V. Connect Pt100 probes to J4/J5 using equal-length three-wire leads. Supply instruments from the protected sensor branch; for AI1–AI3 leave connector pin 1 insulated, connect signal to pin 2 and return to pin 3. Low-side outputs drive the selected SSR input and intermediate relays, not mains loads.

230 V L/N → isolator Q0 → Type A RCBO QF0 → heater breaker QF1 → K1 → K2 → heater, with SSR1 in the L conductor after K2. Both contactors interrupt L and N. PE runs continuously to the cabinet, tank, pump and heater. Keep AC, 24 V, RTD and analog wiring in separate terminal groups and routes; do not bridge N to 0 V.

STB health, low-level health and pressure health feed SR1 through the independent hardware permit chain. Emergency-stop channels and contactor mirror contacts feed the restart monitor. Filling uses a normally closed valve with emergency-stop and high-level power interruption. Restoring a permit requires a deliberate reset and a separate start command.

Tank reference: 316L, inner Ø400 × 800 mm, 2 mm shell / 3 mm bottom, 25 mm insulation and 250 mm legs. H0 is the internal bottom. Heater H100; independent STB probes H160; low level H250; process Pt100 H300; working level H560; high level H680; overflow H720. Independent DN25 vent and overflow remain open, with an unsealed lid.

Use a short DN15 circulation loop, total length ≤2 m and ≤4 bends. Allow 5D upstream / 2D downstream of the flow meter. Keep the fill filter and check valve out of the low-head circulation loop. The selected pump must produce the required ≥3 L/min with the installed piping. SM6120 requires water conductivity ≥20 µS/cm; use a different measurement method for deionized water.

HMI & communication

Weintek MT8072iP V2: 800 × 480 display, 192 × 138 mm panel cutout, 24 V supply. COM2 two-wire RS485 uses 19200 baud, 8E1, slave 1 and zero-based Modbus addressing. DB9 pin 2 D+ → J15.1 A; pin 1 D− → J15.2 B; pin 5 reference → J15.3 GND_ISO. Fit 120 Ω termination only at the two bus ends; bond the cable shield at the cabinet side.

Read holding registers 0–11 with FC03. Write the temperature setpoint at PDU 256 and a single command at 257 with FC06; command 1=start, 2=stop, 3=reset. Do not use FC16. Refresh every 500 ms; after three consecutive communication timeouts show stale data and inhibit start/setpoint writes. The operator screen does not replace the independent hardware permit chain.

PDU addressValueScale / action
0 / 1State / fault bitsEnumeration / bitmask
2 / 3Main / cross-check liquid temperature0.01 °C; invalid = 0x8000
4Pressure0.0001 MPa
5 / 6Level / flow0.01 % / 0.01 L/min
7 / 8Setpoint / heating output0.01 °C / 0.01 %
9 / 10 / 11DO bits / DI bits / firmware versionBitmask / hexadecimal
256Setpoint write · FC0620–85 °C; 0.01 °C; RAM parameter
257Command write · FC061 start / 2 stop / 3 reset

Sizing & calibration

Heating load

3,000 W / 230 V = 13.04 A nominal heater current. For 70 kg of water from 20 to 65 °C, Q = m·cp·ΔT = 13.17 MJ; at 3 kW the ideal heating time is about 73 min. Heat losses, piping and mixing increase real heating time.

Hydrostatic level

h = p / (ρ·g). With ρ = 980 kg/m³ and 0–100 mbar mapped to 4–20 mA, 800 mm corresponds to about 16.30 mA. Calibrate empty, working and upper levels on the actual tank; water density changes with temperature.

Cabinet power & cooling

HDR-100-24 supplies 24 V / 3.83 A (92 W). The design load budget is ≤3.1 A; set DC4 for the safety chain to 2 A and the other four protected branches to 1 A. Fan thermostat starts at 35 °C; size airflow and SSR derating for a cabinet temperature ≤40 °C.

Technical downloads

HMI native-project integration and manufacturing release remain open. The downloadable firmware images are EVT candidates, not production-release images. Download the complete KiCad, firmware, HMI, mechanical, wiring and factory documentation bundle, or choose individual files. The engineering handbook and purchasing workbook are in Chinese; interface tables use common signal names and model codes. File sizes and SHA-256 checksums are supplied for verification.

Application questions

Can I switch a 230 V heater directly from the board?

Use the external SSR and contactors. The PCB uses 24 V field control and low-side outputs for the selected SSR input / relay coils. Follow the cabinet wiring file for the mains circuit.

Can I use a sealed or pressurized tank?

This system example is an atmospheric clean-water tank with separate open vent and overflow. A pressure vessel or a different medium requires a different mechanical, sensor and protection specification.

What changes when the tank or heater gets larger?

Recalculate thermal energy, heater current and surface loading, select a matching SSR / contactor / cable / breaker combination, and size the pump from the complete loop resistance. Reposition the liquid-level and temperature instruments, then adjust limits and PI parameters.

Discuss a process-control project

Share the tank volume, medium, temperature range, heater supply and power, circulation flow, cabinet dimensions, operator-panel requirements and target quantity. These inputs define the board, harness, power cabinet and mechanical scope.